Plant Controller: VAR2
Following checks and corrections are applied during Validation and AutoCorrection.
- KPvar and KIvar: KPvar can't be 0 if KIvar= 0, if true then KPvar changed to 1.
Mult represents the user-specified value Minimum time constant size as multiple of time step option on the Validation page of the Transient Stability Dialog
TimeStep represents the integration time step being used as described on TimeStep
Model Equations and/or Block Diagrams
Parameters:
| QREF | VAR controller reference setpoint, pu |
| VITmin | VAR controller minimum terminal current limit, pu |
| VVTmin | VAR controller minimum terminal voltage limit, pu |
| VVTmax | VAR controller maximum terminal voltage limit, pu |
| KPvar | VAR controller proportional gain, pu |
| KIvar | VAR controller integral gain, pu/sec. |
| VVARLMT | VAR controller output limit, pu |